Parameter Details
2
2.8 H: Terminal Function Selection
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 315
Note:
For information on the comparator function, refer to 66: Comparator1 on page 330 and 67: Comparator2 on page 331.
H2-28: Comparator 2 Upper Limit
No.
(Hex.)
Name Description
Default
(Range)
H2-28
(1548)
Comparator 2 Upper Limit
Sets the upper limit detection level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 330 and 67: Comparator2 on page 331.
H2-29: Comparator 2 Hysteresis
No.
(Hex.)
Name Description
Default
(Range)
H2-29
(1549)
Comparator 2 Hysteresis
Sets the hysteresis level for comparator 2 as a percentage of the full scale analog output for the
monitor selected in H2-26 [Comparator 2 Monitor Selection].
0.0%
(0.0 - 10.0%)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 330 and 67: Comparator2 on page 331.
H2-30: Comparator 2 On-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-30
(154A)
Comparator 2 On-Delay
Time
Sets the on-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 330 and 67: Comparator2 on page 331.
H2-31: Comparator 2 Off-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-31
(154B)
Comparator 2 Off-Delay
Time
Sets the off-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 330 and 67: Comparator2 on page 331.
H2-32: Comparator 1 Filter Time
No.
(Hex.)
Name Description
Default
(Range)
H2-32
(159A)
Comparator 1 Filter Time
Sets the time constant that is applied to the primary delay filter used for the analog output of the
monitor selected with H2-20 [Comparator 1 Monitor Selection].
0.0s
(0.0 - 10.0 s)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 330 and 67: Comparator2 on page 331.
H2-33: Comparator1 Protection Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-33
(159B)
Comparator1 Protection
Selection
Sets drive operation when it detects CP1 [Comparator1 Limit Fault].
4
(0 - 4)
0 : Ramp to Stop
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents