Parameter Details
2
2.8 H: Terminal Function Selection
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 319
0: During Run
Setting Value Function Description
0 During Run
The terminal activates when you input a Run command and when the drive is outputting voltage.
Figure 2.68 Drive Running Time Chart
ON : Drive is running
The drive is receiving a Run command or outputting voltage.
OFF : Drive is stopping
1: Zero Speed
Setting Value Function Description
1 Zero Speed
The terminal activates when the output frequency is less than E1-09 [Minimum Output Frequency] or b2-01 [DC Injection/Zero
SpeedThreshold].
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the reference.
A1-02 Setting Control Method Selection Parameter Used as the Reference
0 V/f E1-09
2 OLV b2-01
5 OLV/PM E1-09
6 AOLV/PM E1-09
8 EZOLV E1-09
Figure 2.69 Zero Speed Time Chart
ON : Output frequency < value of E1-09 or b2-01.
OFF : Output frequency value of E1-09 or b2-01.
2: Speed Agree 1
Setting Value Function Description
2 Speed Agree 1
The terminal activates when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree Detection Width].
Note:
The detection function operates in the two motor rotation directions.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV