2.8 H: Terminal Function Selection
320 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
Figure 2.70 Speed Agree 1 Time Chart
ON : The output frequency is in the range of “frequency reference ± L4-02”.
OFF : The output frequency does not align with the frequency reference although the drive is
running.
3: User-Set Speed Agree 1
Setting Value Function Description
3 User-Set Speed Agree 1
The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02 [Speed Agree
Detection Width] and in the range of the frequency reference ± L4-02.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.
ON : The output frequency is in the range of L4-01 ± L4-02 and the range of frequency reference ±
L4-02.
OFF : The output frequency is not in the range of L4-01 ± L4-02 nor the range of frequency
reference ± L4-02.
Figure 2.71 User-Defined Speed Agree 1 Time Chart
4: Frequency Detection 1
Setting Value Function Description
4 Frequency Detection 1
The terminal deactivates when the output frequency is higher than the value of L4-01 [Speed Agree Detection Level] + L4-02
[Speed Agree Detection Width]. After the terminal deactivates, the terminal stays deactivated until the output frequency = L4-01.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV