Parameter Details
2
2.8 H: Terminal Function Selection
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 321
ON : The output frequency is less than the value of L4-01 or does not exceed the value of L4-01 + L4-
02.
OFF : The output frequency is higher than the value of L4-01 + L4-02.
Figure 2.72 Frequency Detection 1 Time Chart
Note:
Figure 2.72 shows the result of the configuration when L4-07 = 1 [Speed Agree Detection Selection = Detection Always Enabled]. The
default setting of L4-07 is 0 [No detection during baseblock]. When the speed agreement detection selection is No Detection during
Baseblock, the terminal is deactivated when the drive output stops.
5: Frequency Detection 2
Setting Value Function Description
5 Frequency Detection 2
The terminal activates when the output frequency is higher than the value of L4-01 [Speed Agree Detection Level]. After the
terminal activates, the terminal stays activated until the output frequency is at the value of L4-01 - L4-02.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.
ON : The output frequency is higher than the value of L4-01.
OFF : The output frequency is less than the value of L4-01 - L4-02,” or it is not more than the value
of L4-01.
Figure 2.73 Frequency Detection 2 Time Chart
6: Drive Ready
Setting Value Function Description
6 Drive Ready
The terminal activates when the drive is ready and running.
The terminal deactivates in these conditions:
When the power supply is OFF
During a fault
When there is problem with the control power supply
When there is a parameter setting error and the drive cannot operate although there is a Run command
When you enter a Run command and it immediately triggers an overvoltage or undervoltage fault because the drive
has an overvoltage or undervoltage fault during stop
When the drive is in Programming Mode and will not accept a Run command
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV