2.8 H: Terminal Function Selection
328 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
Tells you about the maintenance period for these items:
IGBT
Cooling Fan
Capacitor
Soft charge bypass relay
30: During Torque Limit
Setting Value Function Description
30 During Torque Limit
The terminal activates when the torque reference is the torque limit set with L7 parameters or H3-02 or H3-10 [MFAI Function
Selection].
Note:
Refer to L7: Torque Limit on page 394 for more information.
37: During Frequency Output
Setting Value Function Description
37 During Frequency Output
The terminal activates when the drive outputs frequency.
ON : The drive is outputting frequency.
OFF : The drive is not outputting frequency.
Note:
The terminal deactivates in these conditions:
During Stop
During Baseblock
During DC Injection Braking (initial excitation)
During Short Circuit Braking
Pole Position Detection Complete
Figure 2.79 Active Frequency Output Time Chart
38: Drive Enabled
Setting Value Function Description
38 Drive Enabled
This terminal activates when the H1-xx = 6A [Drive Enable] terminal activates.
39: Watt Hour Pulse Output
Setting Value Function Description
39 Watt Hour Pulse Output
Outputs the pulse that shows the watt hours.
Note:
Refer to H2-06: Watt Hour Output Unit Selection on page 312 for more information.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV