Parameter Details
2
2.8 H: Terminal Function Selection
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 329
■ 3C: LOCAL Control Selected
Setting Value Function Description
3C LOCAL Control Selected
The terminal activates when the Run command source or frequency reference source is LOCAL.
ON : LOCAL
The keypad is the Run command source or the frequency reference source.
OFF : REMOTE
The Run command source or frequency reference source is an external source set with b1-01 [Frequency Reference
Selection 1], b1-15 [Frequency Reference Selection 2], b1-02 [Run Command Selection 1], or b1-16 [Run Command
Selection 2].
■ 3D: During Speed Search
Setting Value Function Description
3D During Speed Search
The terminal activates when the drive is doing speed search.
Note:
Refer to b3: Speed Search on page 170 for more information.
■ 3E: PID Feedback Low
Setting Value Function Description
3E PID Feedback Low
The terminal activates when the drive detects FbL [PID Feedback Loss].
The drive detects FbL [PID Feedback Loss] when the PID feedback value < b5-13 [PID Feedback Loss Detection
Lvl] for longer than b5-14 [PID Feedback Loss Detection Time].
Note:
Refer to PID Feedback Loss Detection on page 183 for more information.
■ 3F: PID Feedback High
Setting Value Function Description
3F PID Feedback High
The terminal activates when the drive detects FbH [Excessive PID Feedback].
The drive detects FbH [Excessive PID Feedback] when the PID feedback value > b5-36 [PID High Feedback
Detection Lvl] for longer than b5-37 [PID High Feedback Detection Time].
Note:
Refer to PID Feedback Loss Detection on page 183 for more information.
■ 4A: During KEB Ride-Thru
Setting Value Function Description
4 A During KEB Ride-Thru
The activates during KEB Ride-Thru.
Note:
Refer to KEB Ride-Thru Function on page 364 for more information.
■ 4B: During Short Circuit Braking
Setting Value Function Description
4B During Short Circuit Braking
The terminal activates during Short Circuit Braking.