3.5 Auto-Tuning
478 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
Precautions before Stationary Auto-Tuning for Line-to-Line Resistance and Stator
Resistance Auto-Tuning
In V/f control, when the motor cable is 50 meters (164 feet) or longer, do Stationary Auto-Tuning for Line-to-Line
Resistance.
WARNING! Electrical Shock Hazard. During Auto-Tuning, the motor will receive high voltage when the motor is stopped. Do not
touch the motor until Auto-Tuning is complete. If you touch a motor that is energized, it can cause serious injury or death.
Precautions before Using Deceleration Rate Tuning and KEB Tuning
Before Deceleration Rate Tuning or KEB Tuning, check these items:
Note:
Do not do Deceleration Rate Tuning if you use a braking resistor unit or a regenerative converter.
Do Deceleration Rate Tuning and KEB Tuning with the load attached to the motor.
Do not do Deceleration Rate Tuning or KEB Tuning for these applications:
In Deceleration Rate Tuning and KEB Tuning, the drive will automatically rotate the motor forward and accelerate and decelerate the motor
again and again.
On a machine that does not let the motor rotate forward
In applications with a small range of operation (trolleys and other such applications that can only move linearly)
Applications where sudden acceleration and sudden deceleration are not applicable.
To do KEB Tuning with the external main circuit capacitors connected to the drive, set L3-26 [Additional DC Bus Capacitors] then do KEB
Tuning.
Do not do KEB Tuning or Deceleration Rate Tuning if the drive is set to use H1-xx = 16 [MFDI Function Select = Motor 2 Selection].
Failure to obey can cause an ov [Overvoltage] fault.