Troubleshooting
2
2.4 Fault
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting 111
Code Name Causes Possible Solutions
SEr Speed Search Retries Exceeded
The speed search-related parameters are set
incorrectly.
• Decrease b3-10 [Speed Estimation Detection Gain].
• Increase b3-17 [Speed Est Retry Current Level].
• Increase b3-18 [Speed Est Retry Detection Time].
• Do Auto-Tuning again.
The motor is coasting in the opposite direction of the
Run command.
Set b3-14 = 1 [Bi-directional Speed Search = Enabled].
Note:
• The drive detects this error if the number of speed search restarts is more than b3-19 [Speed Search Restart Attempts].
• Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
STPo Motor Step-Out Detected
The motor code is set incorrectly for PM Control
Methods.
• Set E5-01 [PM Motor Code Selection] correctly as specified by
the motor.
• For specialized motors, refer to the motor test report and set E5-
xx correctly.
The load is too large. • Increase the value set in n8-55 [Motor to Load Inertia Ratio].
• Increase the value set in n8-51 [Pull-in Current @ Acceleration].
If the drive detects STPo during deceleration when increasing the
value set in n8-51, set the value of n8-79 [Pull-in Current @
Deceleration] lower than n8-51.
• Decrease the load.
• Replace the drive and motor with larger capacity models.
The load inertia is too large. Increase the value set in n8-55.
The acceleration/deceleration times are too short. • Increase the values set in C1-01 to C1-08 [Acceleration/
Deceleration Times].
• Increase the value set in C2-01 [S-Curve Time @ Start of Accel].
Speed response is too slow. Increase the value set in n8-55.
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
SvE Zero Servo Fault
The value set in the torque limit is too small. Adjust torque limit-related parameters L7-01 to L7-04.
The load torque is too large. Decrease the load torque.
Noise interference along the encoder cable Isolate the encoder cable from the drive output line or a different
source of electrical interference.
Note:
• The drive detects this error if motor rotation position moves during Zero Servo.
• Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
TiM Keypad Time Not Set
There is a battery in the keypad, but the date and time
are not set.
Use the keypad to set the date and time.
Note:
• Do a Fault Reset to clear the fault.
• Parameter o4-24 [bAT Detection Selection] enables and disables TiM detection.
Code Name Causes Possible Solutions
UL3 Undertorque Detection 1
A fault occurred on the machine.
Example: There is a broken pulley belt.
Examine the machine and remove the cause of the fault.
The parameters are incorrect for the load. Adjust L6-02 [Torque Detection Level 1] and L6-03 [Torque
Detection Time 1] settings.
Note:
• The drive detects this error if the drive output current is less than the level set in L6-02 for longer than L6-03.
• Do a Fault Reset to clear the fault.
• If the drive detects this error, it will operate the motor as specified by the Stopping Method set in L6-01 [Torque Detection Selection 1].
Code Name Causes Possible Solutions
UL4 Undertorque Detection 2
A fault occurred on the machine.
Example: There is a broken pulley belt.
Examine the machine and remove the cause of the fault.
The parameters are incorrect for the load. Adjust L6-05 [Torque Detection Level 2] and L6-06 [Torque
Detection Time 2] settings.
Note:
• The drive detects this error if the drive output current is less than the level set in L6-05 for longer than L6-06.
• Do a Fault Reset to clear the fault.
• If the drive detects this error, it will operate the motor as specified by the Stopping Method set in L6-04 [Torque Detection Selection 2].