Electrical Installation
5
5.3 Main Circuit Wiring
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting 355
Figure 5.22 Configuration of Main Circuit Terminal Block (T477, T720)
◆ Main Circuit Terminal Functions
Refer to Table 5.2 for the functions of drive main circuit terminals.
Table 5.2 Main Circuit Terminal Functions
Terminal Name
Function
Model
2004 - 2082 2110 - 2138 2169 - 2415 -
4002 - 4044 4060 - 4168 4208 - 4414 4477 - 4720
R/L1
Main circuit power supply input
To connect a commercial
power supply.
S/L2
T/L3
U/T1
Drive output To connect a motor.V/T2
W/T3
B1
Braking resistor connection -
To connect a braking resistor
or braking resistor unit.
B2
+2
• DC power supply input
(+1 and -)
• DC reactor connection
(+1 and +2)
-
To connect peripheral
devices, for example:
• DC power input
• Braking Unit
• DC Link Choke
Note:
Remove the jumper
between terminals +1
and +2 to connect a DC
link choke.
+1
DC power supply input (+1
and -)
• DC power supply input (+1 and -)
• Braking unit connection (+3 and -)
-
+3 -
• 200 V: D class grounding (ground to 100 Ω or less)
• 400 V: C class grounding (ground to 10 Ω or less)
To ground the drive.
Note:
Use terminals - and B1 to connect a CDBR-type control unit to drive models 2004 to 2138 and 4002 to 4168 that have built-in braking
transistors.