3.10 H: Terminal Functions
206 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Setting Value Function Description
17F !PID Bi-Directional Enable
Switches the PID Bi-Directional output to enable or disable.
ON : Disable
OFF : Enabled
19F !DWEZ Disable
Switches the DriveWorksEZ program saved in the drive to enable or disable.
ON : Enabled
OFF : Disable
Note:
Set A1-07 = 2 [DriveWorksEZ Function Selection = Digital input] to use this function.
◆ H2: MFDO
No.
(Hex.)
Name Description
Default
(Range)
H2-01
(040B)
Term M1-M2 Function
Selection
Sets the function for MFDO terminal M1-M2.
Note:
When you do not use the terminal or when you use the terminal in through mode, set this
parameter to F.
0
(0 - 1FF)
H2-02
(040C)
Term M3-M4 Function
Selection
Sets the function for MFDO terminal M3-M4.
Note:
When you do not use the terminal or when you use the terminal in through mode, set this
parameter to F.
1
(0 - 1FF)
H2-03
(040D)
Term M5-M6 Function
Selection
Sets the function for MFDO terminal M5-M6.
Note:
When you do not use the terminal or when you use the terminal in through mode, set this
parameter to F.
2
(0 - 1FF)
H2-06
(0437)
Watt Hour Output Unit
Selection
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection = Watt
Hour Pulse Output].
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
0
(0 - 4)
H2-07
(0B3A)
Modbus Register 1 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
H2-08
(0B3B)
Modbus Register 1 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
H2-09
(0B3C)
Modbus Register 2 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
H2-10
(0B3D)
Modbus Register 2 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
H2-20
(1540)
Comparator 1 Monitor
Selection
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For example, set
H2-20 = 102 to monitor U1-02 [Output Frequency].
102
(000 - 999)
H2-21
(1541)
Comparator 1 Lower Limit
Sets the lower limit detection level for comparator 1 when the full scale analog output for the monitor
selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
H2-22
(1542)
Comparator 1 Upper Limit
Sets the upper limit detection level for comparator 1 when the full scale analog output for the monitor
selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
H2-23
(1543)
Comparator 1 Hysteresis
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output for the
monitor selected in H2-20 [Comparator 1 Monitor Selection].
0.0%
(0.0 - 10.0%)
H2-24
(1544)
Comparator 1 On-Delay
Time
Sets the on-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)