3.5 b: Application
◆ b1: Operation Mode Selection
No.
(Hex.)
Name Description
Default
(Setting Range)
b1-01
(0180)
Frequency Reference
Selection 1
Sets the input method for the frequency reference.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
4 : Pulse Train Input
1
(0 - 4)
b1-02
(0181)
Run Command Selection 1
Sets the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : Memobus/Modbus Communications
3 : Option PCB
1
(0 - 3)
b1-03
(0182)
Stopping Method Selection
Sets the method to stop the motor after removing a Run command or entering a Stop command.
Note:
When A1-02 = 3, 4, 5, 6, 7, 8 [Control Method Selection = CLV, AOLV, OLV/PM, AOLV/PM,
CLV/PM, EZOLV], the setting range is 0, 1, 3.
0 : Ramp to Stop
1 : Coast to Stop
2 : DC Injection Braking to Stop
3 : Coast to Stop with Timer
0
(0 - 3)
b1-04
(0183)
Reverse Operation Selection
Sets the reverse operation function. Disable reverse operation in fan or pump applications where
reverse rotation is dangerous.
0 : Reverse Enabled
1 : Reverse Disabled
0
(0, 1)
b1-05
(0184)
Operation Below Minimum
Freq
Sets the drive operation when the frequency reference decreases to less than the value set in E1-09
[Minimum Output Frequency].
0 : Operate at Frequency Reference
1 : Baseblock (Motor Coasts)
2 : Operate at Minimum Frequency
3 : Operate at Zero Speed
0
(0 - 3)
b1-06
(0185)
Digital Input Reading
Sets the number of times that the drive reads the sequence input command to prevent malfunction
because of electrical interference.
0 : Single Scan
1 : Double Scan
1
(0, 1)
b1-07
(0186)
LOCAL/REMOTE Run
Selection
Sets drive response to an existing Run command when the drive receives a second Run command
from a different location.
0 : Disregard Existing RUN Command
1 : Accept Existing RUN Command
0
(0, 1)
b1-08
(0187)
Run Command Select in
PRG Mode
Sets the conditions for the drive to accept a Run command entered from an external source when
using the keypad to set parameters.
0 : Disregard RUN while Programming
1 : Accept RUN while Programming
2 : Allow Programming Only at Stop
0
(0 - 2)
b1-09
(0188)
Expert
LOCAL/REMOTE Select
during RUN
Sets the function that lets you use the during operation to switch between LOCAL and
REMOTE Modes.
0 : Disabled
1 : Enabled
0
(0, 1)