3.5 b: Application
164 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
No.
(Hex.)
Name Description
Default
(Range)
b5-63
(119C)
PID Differential FB Monitor
Sel
Selects the monitor (Ux-xx) used as the PID Differential Feedback. Set the x-xx part of the Ux-xx
[Monitor].
000
(000 - 999)
b5-64
(119D)
PID Differential FB Monitor
Gain
Sets the gain for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
1.00
(0.00 - 10.00)
b5-65
(119F)
PID Differential FB Monitor
Bias
Sets the bias for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
0.00
(-10.00 - +10.00)
b5-66
(11DE)
PID Feedback Monitor Level
Sets the signal level for the monitor specified in b5-55 [PID Feedback Monitor Selection].
0 : Absolute
1 : Bi-directional (+/-)
0
(0, 1)
b5-67
(11DF)
PID Differential FB Monitor
Lvl
Sets the signal level for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
0 : Absolute
1 : Bi-directional (+/-)
0
(0, 1)
b5-89
(0B89)
RUN
Sleep Method Selection
Sets sleep and wake up operation when using PID.
0 : Standard
1 : EZ Sleep/Wake-up
0
(0, 1)
b5-90
(0B90)
EZ Sleep Unit
Sets the measurement units for b5-91 [EZ Sleep Minimum Speed] and b5-92 [EZ Sleep Level].
0 : 0.1Hz units
1 : rev/min
0
(0, 1)
b5-91
(0B91)
RUN
EZ Sleep Minimum Speed
Sets the minimum speed for the EZ Sleep/Wakeup function. This parameter uses the largest value
from b5-91, b5-34 [PID Output Lower Limit Level], and d2-02 [Frequency Reference Lower Limit].
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
b5-92
(0B92)
RUN
EZ Sleep Level
Sets the value that the output frequency or motor speed must be less than for longer than b5-93 [EZ
Sleep Time] to enter Sleep Mode.
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
b5-93
(0B93)
RUN
EZ Sleep Time
Sets the length of time that the output frequency or motor speed must be less than b5-92 [EZ Sleep
Level] to enter Sleep Mode.
5.0 s
(0.0 - 1000.0 s)
b5-94
(0B94)
RUN
EZ Sleep Wake-up Level
Sets the level at which the drive resumes operation when exiting Sleep Mode.
0.00%
(0.00 - 600.00%)
b5-95
(0B95)
EZ Sleep Wake-up Mode
Sets the wake-up mode to use when exiting Sleep Mode.
0 : Absolute
1 : Setpoint Delta
0
(0, 1)
b5-96
(0B96)
RUN
EZ Sleep Wake-up Time
Sets the EZ Wake-up time.
1.0 s
(0.0 - 1000.0 s)
◆ b6: Dwell Function
No.
(Hex.)
Name Description
Default
(Range)
b6-01
(01B6)
Dwell Reference at Start
Sets the output frequency that the drive will hold momentarily when the motor starts.
0.0
(Determined by A1-02)
b6-02
(01B7)
Dwell Time at Start
Sets the length of time that the drive will hold the output frequency when the motor starts.
0.0 s
(0.0 - 10.0 s)
b6-03
(01B8)
Dwell Reference at Stop
Sets the output frequency that the drive will hold momentarily when ramping to stop the motor.
0.0
(Determined by A1-02)
b6-04
(01B9)
Dwell Time at Stop
Sets the length of time for the drive to hold the output frequency when ramping to stop the motor.
0.0 s
(0.0 - 10.0 s)