Troubleshooting
2
2.5 Minor Faults/Alarms
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting 119
Code Name Causes Possible Solutions
LT-1 Cooling Fan Maintenance Time
The cooling fan is at 90% of its expected performance
life.
1. Replace the cooling fan.
2. Set o4-03 = 0 [Fan Operation Time Setting = 0 h] to reset the
cooling fan operation time.
Note:
When the estimated performance life is expired, the terminal set to H2-01 to H2-03 = 2F [MFDO Function Selection = Maintenance Notification] will activate.
Code Name Causes Possible Solutions
LT-2 Capacitor Maintenance Time
The capacitors for the main circuit and control circuit
are at 90% of expected performance life.
Replace the control board or the drive. For information about
replacing the control board, contact Yaskawa or your nearest sales
representative.
Note:
When the estimated performance life is expired, the terminal assigned to H2-01 to H2-03 = 2F [MFDO Function Select = Maintenance Notification] will be ON.
Code Name Causes Possible Solutions
LT-3 SoftChargeBypassRelay MainteTime
The soft charge bypass relay is at 90% of its expected
performance life.
Replace the control board or the drive. For information about
replacing the control board, contact Yaskawa or your nearest sales
representative.
Note:
When the estimated performance life is expired, the terminal assigned to H2-01 to H2-03 = 2F [MFDO Function Select = Maintenance Notification] will be ON.
Code Name Causes Possible Solutions
LT-4 IGBT Maintenance Time (50%)
The IGBT is at 50% of its expected performance life. Check the load, carrier frequency, and output frequency.
Note:
When the estimated performance life is expired, the terminal assigned to H2-01 to H2-03 = 2F [MFDO Function Select = Maintenance Notification] will be ON.
Code Name Causes Possible Solutions
oH Heatsink Overheat
The ambient temperature is high and the heatsink
temperature is more than the L8-02 [Overheat Alarm
Level].
Measure the ambient temperature.
Increase the airflow around the drive.
Install a cooling device (cooling fan or air conditioner) to lower
the ambient temperature.
Remove objects near the drive that are producing too much heat.
There is not sufficient airflow around the drive. Give the drive the correct installation space as shown in the
manual.
Make sure that there is sufficient circulation around the control
panel.
Examine the drive for dust or other unwanted materials that
could clog the cooling fan.
Remove unwanted materials that prevent air circulation.
The internal cooling fan or fans have stopped. 1. Use the procedures in this manual to replace the cooling fan.
2. Set o4-03 = 0 [Fan Operation Time Setting = 0 h] to reset the
cooling fan operation time.
Note:
The drive detects this error if the heatsink temperature of the drive is more than L8-02.
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Set the stopping method for this fault in L8-03 [Overheat Pre-Alarm Selection].
Code Name Causes Possible Solutions
oH2 External Overheat (H1-XX=B)
An external device sent an oH2. 1. Find the external device that output the overheat alarm.
2. Remove the cause of the problem.
3. Clear the Overheat Alarm (oH2) [H1-xx = B] that was set to
MFDI terminals S1 to S6.
Note:
If the drive detects this error, the terminal set to H2-01 to H2-02 = 10 [MFDO Function Selection = Alarm] will activate.
Code Name Causes Possible Solutions
oH3 Motor Overheat (PTC Input)
The thermistor wiring that detects motor temperature
is defective.
Correct wiring errors.
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault