Troubleshooting
2
2.6 Parameter Setting Errors
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting 129
Code Name Causes Possible Solutions
oPE33 Digital Output Selection Error
These two parameters are set at the same time:
H2-60 F [Term M1-M2 Secondary Function
Not Used]
H2-01 = 1xx [Term M1-M2 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
H2-63 F [Term M3-M4 Secondary Function
Not Used]
H2-02 = 1xx [Term M3-M4 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
H2-66 F [Term M5-M6 Secondary Function
Not Used]
H2-03 = 1xx [Term M5-M6 Function Selection =
Inverse output of xx]
Clear the H2-01 to H2-03 = 1xx [Inverse output of xx] settings.
Note:
It is not possible to set H2-01 to H2-03 = 1xx [Inverse output of
xx] when using output functions for logic operations (H2-60,
H2-63, H2-66 F).
These parameter pairs are set incorrectly:
H2-21 [Comparator 1 Lower Limit] > H2-22
[Comparator 1 Upper Limit]
H2-27 [Comparator 2 Lower Limit] > H2-28
[Comparator 2 Upper Limit]
Set parameters H2-21 H2-22.
Set parameters H2-27 H2-28.