3.10 H: Terminal Functions
208 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
No.
(Hex.)
Name Description
Default
(Range)
H2-63
(1B49)
Expert
Term M3-M4 Secondary
Function
Sets the second function for terminal M3-M4. Outputs the logical calculation results of the terminals
assigned to functions by H2-02 [Term M3-M4 Function Selection].
F
(0 - FF)
H2-64
(1B4A)
Expert
Terminal M3-M4 Logical
Operation
Sets the logical operation for the functions set in H2-02 [Term M3-M4 Function Selection] and H2-
63 [Term M3-M4 Secondary Function].
0
(0 - 8)
H2-65
(1B4B)
Expert
Terminal M3-M4 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal M3-M4.
0.1 s
(0.0 - 25.0 s)
H2-66
(1B4C)
Expert
Term M5-M6 Secondary
Function
Sets the second function for terminal M5-M6. Outputs the logical calculation results of the terminals
assigned to functions by H2-03 [Terminal M5-M6 Function Select].
F
(0 - FF)
H2-67
(1B4D)
Expert
Terminal M5-M6 Logical
Operation
Sets the logical operation for the functions set in H2-03 [Term M5-M6 Function Selection] and H2-
66 [Term M5-M6 Secondary Function].
0
(0 - 8)
H2-68
(1B4E)
Expert
Terminal M5-M6 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal M5-M6.
0.1 s
(0.0 - 25.0 s)
■ H2-xx: MFDO Setting Values
Setting Value Function Description
0 During Run
The terminal activates when you input a Run command and when the drive is outputting voltage.
ON : Drive is running
OFF : Drive is stopping
1 Zero Speed
The terminal activates when the output frequency < E1-09 [Minimum Output Frequency] or b2-01 [DC Injection/Zero
SpeedThreshold].
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the reference.
A1-02 Setting Control method selection Parameter Used as the Reference
0 V/f E1-09
1 CL-V/f E1-09
2 OLV b2-01
3 CLV E1-09
4 AOLV E1-09
5 OLV/PM E1-09
6 AOLV/PM E1-09
7 CLV/PM b2-01
8 EZOLV E1-09
ON : Output frequency < value of E1-09 or b2-01.
OFF : Output frequency ≥ value of E1-09 or b2-01.
2 Speed Agree 1
The terminal turns on when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree Detection Width].
Note:
• The detection function operates in the two motor rotation directions.
• The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed status when A1-
02 = 4 and n4-72 = 1.
ON : The output frequency is in the range of “frequency reference ± L4-02”.
OFF : The output frequency does not align with the frequency reference although the drive is running.