Parameter List
3
3.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting 299
No.
*1
Name Unit Default
- Drive Model - 4605 4720
C6-01
Normal / Heavy Duty
Selection
-
HD ND HD ND
0 1 0 1
o2-04
Drive Model (KVA)
Selection
Hex. 00AE 00AF
E2-11
(E4-11, E5-02)
Motor Rated Power
HP
(kW)
450
(335)
500
(370)
500
(370)
600
(450)
b3-04
V/f Gain during Speed
Search
% 60 60 60 60
b3-06
Speed Estimation
Current Level 1
- 0.7 0.7 0.7 0.7
b3-08
Speed Estimation ACR
P Gain
- 0.8 0.8 0.8 0.8
b3-26
Direction Determination
Level
- 1000 1000 1000 1000
b8-03
Energy Saving Filter
Time
s 2.00 2.00 2.00 2.00
b8-04
Energy Saving
Coefficient Value
- 21.76 23.84 21.76 23.84
C5-17
(C5-37)
Motor Inertia kgm
2
11.00 12.00 11.00 12.00
C6-02
Carrier Frequency
Selection
- 1 7 1 7
E2-01
(E4-01)
Motor Rated Current
(FLA)
A 500 650 500 650
E2-02
(E4-02)
Motor Rated Slip Hz 1.25 1 1.25 1
E2-03
(E4-03)
Motor No-Load Current A 130 130 130 130
E2-05
(E4-05)
Motor Line-to-Line
Resistance
Ω 0.014 0.012 0.014 0.012
E2-06
(E4-06)
Motor Leakage
Inductance
% 20 20 20 20
E2-10
(E4-10)
Motor Iron Loss W 4700 5560 4700 5560
E5-01
PM Motor Code
Selection
- FFFF FFFF FFFF FFFF
L2-02
Power Loss Ride
Through Time
s 2 2 2 2
L2-03
Minimum Baseblock
Time
s 2.1 2.3 2.1 2.3
L2-04
Powerloss V/f Recovery
Ramp Time
s 2 2.2 2 2.2
L2-05
Undervoltage Detection
Lvl (Uv1)
- 380 380 380 380
L3-24
Motor Accel Time @
Rated Torque
s 1.392 1.667 1.392 1.667
L8-02 Overheat Alarm Level °C 133 133 125 125
L8-09
Output Ground Fault
Detection
- 1 1 1 1
L8-38
Carrier Frequency
Reduction
- 2 2 2 2
n1-01
Hunting Prevention
Selection
- 2 2 2 2
n1-03
Hunting Prevention
Time Constant
ms 100 100 100 100