A1-6
PARA- SETTING RANGE SETTING FACTORY USER PARA.
METER NAME (AND UNITS) INCREMENT SETTING SETTING REF.
0: PID control disabled
1: D = Feed Forward
2: D = Feedback
3: Reference + PID (D = Feed Forward)
4: Reference + PID (D = Feedback) 1 0
n128 PID Control Selection 5: Inverse PID - D = Feed Forward
6: Inverse PID - D = Feedback
7: Inverse PID - Reference + PID
(D = Feed Forward)
8: Inverse PID - Reference + PID
(D = Feedback)
n129 PID Feedback Gain note 4 0.00 to 10.00 0.01 1.00
n130 PID Proportional Gain note 4 0.00 to 25.00 0.1 1.0
n131 PID Integral Time note 4 0.00 to 360.00 0.1 s 1.0 5.28
n132 PID Derivative Time note 4 0.00 to 2.50 0.01 0.00
n133 PID Offset Adjustment note 4 -100 to 100 1% 0
n134 Integral Value Limit note 4 -100 to 100 1% 100
n135 PID Output Lag Filter Time note 4 0.0 to 10.0 0.1 s 0.0
Feedback Loss
0: Disabled
n136 1: Enabled - Alarm (operation continues) 1 0
Detection Selection
2: Enabled Fault (coast to stop)
n137
Feedback Loss
Detection Level
0 to 100 1% 0
n138
Feedback Loss
Detection Time
0.0 to 25.5 0.1 s 1.0
0: Energy saving disabled
n139
Energy Saving Selection
1: Energy saving enabled
10note 5
Note: Energy saving becomes enabled by
(Energy Saving)
V/f control mode
n140
Energy Saving Gain
K2 (Energy Saving)
0.00 to 6550 0.1 or 1 Note 1
Energy Saving Voltage
0 to 120 1% 50
n141 Lower Limit at 60 Hz
(Energy Saving)
Energy Saving Voltage
0 to 25 1% 12
n142 Lower Limit at 6 Hz
(Energy Saving)
5.31
n143
Time of Average kW
1 to 200
11
(Energy Saving) (x 24 ms) (24 ms)
n144
Voltage Limit of Tuning
1 to 100 1% 0
(Energy Saving)
n145
Step Voltage of Tuning to
100% Output Voltage 0.1 to 10.0 0.1% 0.5
(Energy Saving)
n146
Step Voltage of Tuning to
5% Output Voltage 0.1 to 10.0 0.1% 0.2
(Energy Saving)
n149 Pulse Train Input Scaling 100 to 3300 1 (x 10 Hz)
3072
5.11
(30,720 Hz)
Output Frequency Monitor:
0: 1440 Hz / Max. output frequency
1: 1f output
6: 6f output
12: 12f output
24: 24f output 0, 1, 6, 12,
n150
Pulse Monitor Output 36: 36f output 24, 36, 40,
0 5.17
Frequency Selection Frequency Reference Monitor: 41, 42, 43,
40: 1440Hz / Max. output frequency 44, 45
41: Frequency reference * 1
42: Frequency reference * 6
43: Frequency reference * 12
44: Frequency reference * 24
45: Frequency reference * 36
0: Fault - Coast to stop
1: Fault - Ramp to stop (n020)
n151
Modbus Time Out
2: Fault - Ramp to stop (n022) 1 0 5.14
Detection
3: Alarm - operation continues
4: Disabled