Sigma II User’s Manual Chapter 5:  Parameter Settings and Functions
5 - 39
Note: Input signal /C-SEL can be used only when a signal is allocated to the input circuit.  See 5.3.3 Input 
Circuit Signal Allocation. 
Pn000.1 Control Method
9
Speed Control:  When /P-CON (/C-SEL) is ON 
Set the parameter Pn002.0 as shown below. 
8
Position Control ⇔ Torque Control 
Can be used to switch between speed (contact reference) and torque control. 
•/P-CON (/C-SEL)(CN1-41) is used to switch control.       
6
Speed Control (Contact Reference) ⇔ Torque Control 
Can be used to switch between speed (contact reference) and torque control. 
•/P-CON (/C-SEL)(CN1-45) and /N-CL(SPD-B)(CN1-46) are used to switch control.   
 
Parameter
Pn002.0
State
Speed Reference 
Input 
(V-REF)
(CN1-5,6)
Torque Reference 
Input
(T-REF)
(CN1-9,10)
Comments
0
Speed Control
Speed Reference Cannot be used.
1
Torque limit speed control by analog voltage 
reference 
See 5.2.9 Speed Feed-Forward 
Function for more details on 
torque limit speed control by 
analog voltage reference. 
Speed Reference Torque Limit
2
Speed control with torque feed-forward See 5.2.8 Torque Feed-Forward 
Function for more details on 
torque feed-forward speed con-
trol. 
Speed reference Torque feed-forward
CN1-41 
State
Selects
Open Position Control
0V Torque Control
Parameter
/P-CL (/SPD-A)
CN1-45
State
Parameter
/N-CL (/SPD-B)
CN1-46
State
0 0 Torque Control
0
1
Speed Control
(Contact reference)
11
10