Sigma II User’s Manual Chapter 5: Parameter Settings and Functions
5-111
MCCB or Fuse According to Power Capacity
The following table shows the MCCB or fuse capacity for each power supply
capacity.
*1
This is the net value at the rated load. When actually selecting fuses, determine the capacity with enough
margin for peak power operation.
*2
Operating characteristics (at 25°C): 2 seconds or more for 200%, 0.01 second or more for 700%
Notes: 1. A fast-operating fuse cannot be used because the servo amplifier power supply is a capacitor
input type. A fast-operating fuse may blow when the power is turned ON.
2. SGDH servo amplifiers do not have built-in ground protection circuits. To configure a safer
system, install a ground fault interrupter with or without a circuit breaker for protection against
overload and short circuit conditions.
Main Circuit
Power
Supply
Servo Amplifier
Model
Applicable Motor
Power Capacity per
Servo Amplifier
(kVA)
*1
Current Capacity per
MCCB or Fuse
(A
rms
)
*1, *2
Capacity
(kW)
SGDH-
Single-phase,
100V
0.03 A3BE SGMAH-A3B 0.15
4
0.05 A5BE SGMAH-A5B 0.25
0.10 01BE
SGMAH-01B
0.40
SGMPH-01B
0.20 02BE
SGMAH-02B
0.60 6
SGMPH-02B
Single-phase,
200V
0.03 A3AE SGMAH-A3A 0.20
4
0.05 A5AE SGMAH-A5A 0.25
0.10 01AE
SGMAH-01A
0.40
SGMPH-01A
0.20 02AE
SGMAH-02A
0.75
SGMPH-02A
0.40 04AE
SGMAH-04A
1.2 8
SGMPH-04A
0.75 08AE-S
SGMAH-08A
2.1 11
SGMPH-08A
1.50 15AE-S SGMPH-15A 4.0 19