2
.
DIGITAL
OPERATOR
(JV0P-114)
(Conttd)
ELECTRONIC
THERMAL
OVERL0~D
PROTECTION
*
The
example
represents
YASKAWA
0
.5HP
(0
.4
kW),
230
V,
4-
pole
motor
.
The
YASKAWA
standard
motor
current
value
is
set
at
factory
prior
to
shipping
.
See
page
86
.
71~
=XX0X
2nd
digit
0
:
Standard
motor
41
:
Exclusive-use
motor
-
109
-
19
=Motor
rated
current
value
Set
the
motor
rated current
value according
to
the
value on
the
motor
nameplate
.
IN
=X
X
X
1
can
make
electronic
thermal overload
function disabled
.
1
st
digit
0
:
Electronic
thermal
overload
protection
provided
1
:
Electronic
thermal overload
protection
not
provided
Motor
output
current
is
detected
by
the
inverter
built-in
electronic
thermal
overload
function,
and
inverter
exclusive-use
motors
or
standard
motors
are
prevented
from
overloading
.
(It
is
not
necessary
to
mount
the
thermal
overload
relay
externally
.
However,
to
connect
several
motors
to
one
inverter,
a
thermal
overload
relay
must
be
inserted
for
each
motor
.
It is
necessary
to
reduce
carrier
frequency
according
to
the
wiring
distance
between
the
inverter
and
motor
when
thermal
overload
relays are
inserted
.
For
details,
refer
to
the
precautions
on
wiring
described
on
page
29
.)
Item
Name
Constant
to
be
Set
Factory
Preset
Motor
Type
1s
0000
Motor
Rated
Current
M~
1
.9
A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed-606PC3 and is the answer not in the manual?

YASKAWA Varispeed-606PC3 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed-606PC3
CategoryInverter
LanguageEnglish

Related product manuals