2
.
DIGITAL
OPERATOR
(JV0P-114)
(Cont'd)
Stall
prevention
during
running
If
the
motor
current
exceeds
the
value
set
to
31
because
of
impact
load during
running,
output
frequency
is
automatically
lowered
.
When
the
motor
current
is
reduced
to
the
[]
set
value
or
less,
the
motor
starts
acceleration
again
and
the
operation
is
continued
.
F201
=ox
x
x
OUTPUT
FREQ
1
MOTOR
CURRENT
4th
di
ait
TIME
Stall
prevention
during
deceleration
Automatically
adjusts
deceleration
rate
with
monitoring
DC
voltage
to
prevent
overvoltage
during
deceleration
.
Set
"1" for
connecting braking
resistor
.
0
:
Stall
prevention
during
deceleration
enabled
1
:
Stall
prevention
during
deceleration
disabled
When
the
motor
load
is
large
or accel/decel
time
is
short,
the
accel/decel
time
may
be
longer
than
the
set
value
because
of
the
stall
preventive
function
.

Table of Contents