7
.
VS-606PC3
INVERTER
MAIN
UNIT
(Cont'd)
(2)
Main
circuit
terminals
Main
circuit
terminal
arrangement
3-phase
series
(all
models)
L1
L2
*
Use
screw
for
frame
ground
.
L3
B1/Q
Table
1
.1
VS-606PC3
Main
Circuit
Terminals
lx~
B2
T1
T2 T3
240
V
single-phase
series
240
V
single-phase
series
NEMA
1
0
.13
to
1
.5
HP
(0
.1
to
1
.5
kW)
3
and
5
HP
(2
.2
and
3
.7
kW)
NEMA4
0
.13
to
2
HP
(0
.1
to
1
.5
kW)
L
1
L2
B1is
B2
T
1
T2
T3
L
1
L2
B1/
D
B2
T
1
T2
T3
BLANK
(Do
not
use
(3)
Molded-case
circuit
breaker
(MCCB)
and
Fuse
for
branch
circuit
protection
Be
sure
to
connect
MCCBs
or
Fuses
between
AC
main
circuit
power
supply
and
VS-606PC3
input terminals
L1,
L2,
L3
to
protect
wiring
.
Recommended
ratings
of
MCCB
and
Fuse
are
listed in
Table
1
.2
.
The
fuses
should be
Listed
Class
RK5
fuses
.
When
a
ground
fault
interrupter
is
used,
select
one
not
influenced
by
high
frequency
.
Setting current
should be
200
mA
or
more
and
operating
time,
0
.1
sec
or
more
to
prevent
malfunctions
.
(Example)
NV
series
by
Mitsubishi
Electric
Co
.,
Ltd
.
(manufactured
in
and
after
1988),
EGSG
series
by
Fuji
Electric
Co
.,
Ltd
.
(manufactured
in
and
after
1984)
-23-
Terminal
Descr
i
pt
i
on
L
1
Main
circuit
power
input
L2
"L
1
",
"L2"
are
used
for
single-phase
input
L3
specifcations
.
T1
T2
Inverter
output
T3
B
1/
p+
Braking
resistor
or
braking
resistor
unit
B2
connector
(options)
Grounding
(ground
resistance
should
be
100
ohms
or
less)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed-606PC3 and is the answer not in the manual?

YASKAWA Varispeed-606PC3 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed-606PC3
CategoryInverter
LanguageEnglish

Related product manuals