Input Description Assignment
Signal evaluation Specify the signal of the connected encoder:
n Pulse/direction At the input count and direction signal
are connected
n At the input there is an encoder connected with the fol-
lowing evaluation:
Rotary encoder single
Rotary encoder double
Rotary encoder quadruple
Pulse/direction
Hardware gate Gate control exclusively via channel 3:
n enabled: The gate control for channel 3 happens via
SW and HW gate
n disabled: The gate control for channel 3 exclusively
happens via SW gate
Ä
Chapter 5.6.6.2 ‘Gate function’ on page 111
disabled
Count direction inverted Invert the input signal ‘Direction’ :
n enabled: The input signal is inverted
n disabled: The input signal is not inverted
disabled
Output Description Assignment
Characteristics of the output The output and the "Comparator" (STS_CMP) status bit
are set, dependent on this parameter
.
n No comparison: The output is used as normal output
and STS_CMP remains reset.
n Comparator
Counter value ³ Comparison value
Counter value £ Comparison value
n Pulse at comparison value
To adapt the used actuators you can specify a
pulse duration. The output is set for the specified
pulse duration when the counter value reaches the
comparison value. When you've set a main
counting direction the output is only set at reaching
the comparison value from the main counting direc-
tion.
No comparison
Pulse duration Here you can specify the pulse duration for the output
signal.
n The pulse duration starts with the setting of the
according digital output.
n The inaccuracy of the pulse duration is less than 1ms.
n There is no past triggering of the pulse duration when
the comparison value has been left and reached again
during pulse output.
n If the pulse duration is changed during operation, it will
take ef
fect with the next pulse.
n If the pulse duration = 0, the output is set until the com-
parison condition is not longer fulfilled.
Range of values: 0...510ms in steps of 2ms
0
VIPA System MICRO
Deployment I/O periphery
Counting > Parametrization
HB400 | CPU | M13-CCF0000 | en | 16-47 102