Order no. M13-CCF0000
Lamp load 10 W
Parallel switching of outputs for redundant control of a load not possible
Parallel switching of outputs for increased power not possible
Actuation of digital input
ü
Switching frequency with resistive load max. 1000 Hz
Switching frequency with inductive load max. 0.5 Hz
Switching frequency on lamp load max. 10 Hz
Internal limitation of inductive shut-off voltage L+ (-45 V)
Short-circuit protection of output yes, electronic
Trigger level 1 A
Number of operating cycle of relay outputs -
Switching capacity of contacts -
Output data size 12 Bit
Technical data analog inputs
Number of inputs 2
Cable length, shielded 200 m
Rated load voltage -
Reverse polarity protection of rated load voltage -
Current consumption from load voltage L+ (without load) -
Voltage inputs
ü
Min. input resistance (voltage range) 100 kΩ
Input voltage ranges 0 V ... +10 V
Operational limit of voltage ranges +/-3.5%
Operational limit of voltage ranges with SFU -
Basic error limit voltage ranges +/-3.0%
Basic error limit voltage ranges with SFU -
Destruction limit voltage max. 30V
Current inputs -
Max. input resistance (current range) -
Input current ranges -
Operational limit of current ranges -
Operational limit of current ranges with SFU -
Basic error limit current ranges -
Radical error limit current ranges with SFU -
Destruction limit current inputs (electrical current) -
Destruction limit current inputs (voltage) -