17-4
IM CW240E
Formula for Each Wiring
Measurement
Item
Wiring
Single Phase 3 Wire
Equations Symbol
Average Voltage Uave ( U1 U2 ) / 2
Iave
( I 1 I 2 ) / 2
PP1P2
QQ1Q2
Average Current
Active Power
Reactive
Power 2
*4
Apparent Power S = U I SS1S2
Power Factor
Reactive power
method not used
*6
PF
Reactive power
method used
PF
Phase Angle
*6
PA
Q = S
2
P
2
PF =
S
P
PA = cos
–1
PF
P
2
Q
2
PF =
P
_
_
_
_
Measurement
Item
Wiring
3 Phase 3 Wire 2 Current
*7
Average Voltage Uave ( U1U2U3 ) / 3
Iave ( I 1I 2 I 3 ) / 3
*2
PP1P3
Q
Average Current
Active Power
Reactive
Power 2
*4
Apparent Power
S U I S
Power Factor
Reactive power
method not used
*6
PF
Reactive power
method used
PF
Phase Angle
*6
PA
PF =
(S1
S3)
S
P
Q = S
2
P
2
S
2
P
2
P
2
Q
2
PF =
PA = cos
–1
PF
P
2
3
Equations
Symbol
_
_
_
_
17.1 CW 240 Specifications