Chapter3InstallationPreparation
Theequipmentroommustcomplywithlocalīæreresistance
standard.
PowerSupplyRequirements
Inspection
PowersupplyrequirementsinspectionincludesDCandACpower
supplyrequirementsinspection.
DCPowerSupplyNominalvoltageofpowersupplyprovidedforZXR108900series
switchbyequipmentroomis-48Vandtheallowedvariationrange
is-57V~-40V .
NoiselevelindicesoftheDCvoltagemustmeetgeneraltechnical
speciīæcationsissuedbytheformerMPT .
DCpowersupplymustbeinstalledwithover-voltage/over-current
protectionandindicators.
ACPowerSupplySingle-phasepowersource:150V~300V ,45Hz~60Hz,wavedis-
tortion<5%.
Voltagefrequencyrequirementsforstandbyelectricgeneratorare
thesameasthoselistedabovebutitswavedistortionrangeis
5%~10%.
GroundingInspection
GroundingInspectionincludesthefollowingitems:
ļæ½Groundwiresintheequipmentroomshouldbearrangedradial
orinplanemode.Groundwiresshouldbewiredseparately.
Electriccircuitsformedbycorrugatedsteelbarsinthebuilding
orviatheracksarenotallowed.
ļæ½Incaseofajointgroundingmode,resistancemustbelessthan
1Ī©.Thesectionalareaofgroundingcabledependsonmaxi-
mumbearablecurrent.Thegroundingcablemustbesheathed
coppercableinsteadofbarecopperwire.
AuxiliaryEquipment
Inspection
AuxiliaryEquipmentInspectionincludesthefollowingitems:
ļæ½DDFandODFframesrelatedtocurrentprojectmusthavebeen
installed.Thecapacitymustbesufīæcientandallopticalcables
musthavebeenlaid.