ZXR108900SeriesHardwareInstallationManual
Thismustnotbelessthan450kg/m
2
.
ļæ½Netheight
NetheightoftheNOCroommustbemorethan3.20m.Ifthe
netheightoftheNOCroomislessthan3.2m,specialinstruc-
tionmustbegiveninprojectdesigndocument,explainingthe
cablerouting.
ļæ½PassagewayofNOCroom
MaindoorsofNOCroommustbebigenoughforhandlingof
equipment,namely,thewidthmustbemorethan1.8m,height
morethan2.2m.Inaddition,thedoorlocksandkeysmustbe
complete.
ļæ½Grooveandholes
Ventilationdevicesmustbeavailable.
Theremustbenopeelingfromceiling,walls,doors,windows
andīooroftheNOCroom.Theremustbenodustrisingor
accumulatedinNOCroom.
Damp-proofmeasuresmustbetakenforallgrooves.Their
corneranglesmustbeeven.Gapsbetweengroundandcover
platesmustbeclose.Inaddition,lighting,powertubesand
cablesmustbeburiedunderground.
ļæ½NOCroomīoor
Patternedmaterialsarenotadoptedforīoorandclear ,simple
andelegantcolorsareappropriateforwallsandceiling.Asfor
thecoating,lusterlesspaintorpaintwithoutsiliconemustbe
used.
Heightofraisedīoormustbe300mmor330mm.Theunitre-
sistanceofraisedīoorsystemmustcomplywithspeciīæcation
forraisedīoorofComputerRooms.Thelaidīoorblocksmust
becloseandīærm.Thehorizontalerrorpersquaremetermust
notbemorethan2mm.
Whenraisedīoorisnotavailable,theconductiveīoormustbe
laid(thevolumeresistancemustbe10~1000MĪ©).Thecon-
ductiveīoororraisedīoormustbegroundedforstaticdis-
charge,whichcanbeconnectedwithgroundingfacilitythrough
acurrent-limitingresistorandconnectioncable.Thecurrent-
limitingresistanceis1MĪ©.
FlooroftheNOCroommustbeevenandclean.Inaddition,the
quantity,locationanddimensionsofreservedclosedconduits,
groovesandholesmustcomplywithprocessdesignrequire-
ments.
IndoorEnvironmentofNOC
RoomInspection
Equipmentroommustbecleanandfreeofdust,corrosivegasesor
wastegases.Nosupplyorsewagewaterpipesareallowedtopass
theequipmentroomandanycontactwithwatermustbeavoided.
10ConīædentialandProprietaryInformationofZTECORPORATION