VCCX2 Controller Technical Guide
BACnet
®
Properties for the VCCX2 Controller
Parameter Object Description
Limits
RSMZ 2
Comp VFD
Drive
Status
AI: 178 Current RSMZ 2
Comp VFD
drive status
See RSMZ
Drive Status Bits on
pages 134-135.
RSMZ 2
Compressor
Current
AI: 179 Current reading in Amps
that the RSMZ 2
compressor is using
RSMZ 2
Discharge
Line Temp
AI: 180 Current RSMZ 2
discharge line
temperature
RSMZ 2
Faults
AI: 181 Current RSMZ 2
Faults
See RSMZ Faults
Bits on
pages 134-135.
RSMZ 2
Lockouts
AI: 182 Current RSMZ 2
Lockouts
See RSMZ Lockouts
Bits on
pages 134-135.
RSMZ 3
Condenser
Fan
AI: 183 Current RSMZ 3
condenser fan signal
RSMZ 3
Reheat
Valve 1
AI: 184 Current RSMZ 3
Reheat Valve 1 position
RSMZ 3
Discharge
Pressure
AI: 185 Current RSMZ 3
discharge
pressure
RSMZ 3
Suction
Pressure
AI: 186 Current RSMZ 3
Suction Pressure
RSMZ 3
Suction Line
Temp
AI: 187 Current RSMZ 3
Suction Line Temperature
RSMZ 3
Saturation
Temp
AI: 188 Current RSMZ 3
Saturation
Temperature
RSMZ 3
Superheat
AI: 189 Current RSMZ 3
Superheat
temperature
RSMZ 3
EEV
Position
AI: 190 Current RSMZ 3
EEV valve
position
RSMZ 3
Suction
Pressure 2
AI: 191 Current RSMZ 3
Suction pressure 2
BACnet
®
Properties for the VCCX2 Controller
Parameter Object Description
Limits
RSMZ 3
Suction Line
Temp 2
AI: 192 Current RSMZ 3
Suction Line
Temperature 2
RSMZ 3
Saturation
Temp 2
AI: 193 Current RSMZ 3
Saturation
Temperature 2
RSMZ 3
Superheat 2
AI: 194 Current RSMZ 3
Superheat
Temperature 2
RSMZ 3
EEV
Position 2
AI: 195 Current RSMZ 3
EEV valve
position 2
RSMZ 3
Warnings
AI: 196 Current RSMZ 3
Warnings
See RSMZ Warnings
Bits on
pages 134-135.
RSMZ 3
Discharge
Line Temp
AI: 197 Current RSMZ 3
discharge line
temperature
RSMZ 3
Faults
AI: 198 Current RSMZ 3
Faults
See RSMZ Faults
Bits on
pages 134-135.
RSMZ 3
Lockouts
AI: 199 Current RSMZ 3
Lockouts
See RSMZ Lockouts
Bits on
pages 134-135.
RSMZ 4
Condenser
Fan
AI: 200 Current RSMZ 4
Condenser Fan Signal
RSMZ 4
VFD
Comp
Perc
AI: 201 Current RSMZ 4
VFD Compressor
Percentage
RSMZ 4
Discharge
Pressure
AI: 202 Current RSMZ 4
Discharge
Pressure
RSMZ 4
Suction
Pressure
AI: 203 Current RSMZ 4
Suction Pressure
RSMZ 4
Suction Line
Temp
AI: 204 Current RSMZ 4
Suction Line
Temperature
RSMZ 4
Saturation
Temp
AI: 205 Current RSMZ 4
Saturation
Temperature
APPENDIX C
-
VCCX2 BACnet
®
VCCX2 BACnet
®
Parameters