Communication with Modbus
A43/A44 112 2CMC48001M0201
User Manual Revision: C
Quantity
Details
Start
Size
Res.
Unit
Value range
Data
reg
type
(Hex)
Power factor
L3
5B3D
1
0,001
-
-1,000-+1,000
Signed
Current quadrant
Total
5B3E
1
-
1-4
Unsigned
Current quadrant
L1
5B3F
1
-
1-4
Unsigned
Current quadrant
L2
5B40
1
-
1-4
Unsigned
Current quadrant
L3
5B41
1
-
1-4
Unsigned
Note Powers are sent out as 32 bit signed integers, expressed in W (or var/VA)
with 2 decimals. This means that the maximum power possible to express is
approximately ±21 MW. If the power is higher than that the user is adviced to read
power from the DMTME mapping instead, where the scaling is in W without
decimals.
Harmonics
Inputs and
outputs
Harmonics are mapped in one register each, starting with THD and then
followed by 2nd, 3rd, 4th harmonic and so on.
All registers in the following table are read only:
Quantity
Details
Start
Size/
Nr of
Res.
Unit
Data type
reg
harmonic
harmonics
(Hex)
Voltage harmonics
L1-N
5D00
1
16
0,1
%
Unsigned
Voltage harmonics
L2-N
5D80
1
16
0,1
%
Unsigned
Voltage harmonics
L3-N
5E00
1
16
0,1
%
Unsigned
Voltage harmonics
L1-L2
5E80
1
16
0,1
%
Unsigned
Voltage harmonics
L3-L2
5F00
1
16
0,1
%
Unsigned
Voltage harmonics
L1-L3
5F80
1
16
0,1
%
Unsigned
Current harmonics
L1
6000
1
16
0,1
%
Unsigned
Current harmonics
L2
6080
1
16
0,1
%
Unsigned
Current harmonics
L3
6100
1
16
0,1
%
Unsigned
Current harmonics
N
6180
1
16
0,1
%
Unsigned
The following table contains both writable and read only registers:
Quantity
Details
Start
Size
Possible values
Data type
Read/
Reg
Write
(Hex)
Output 1
6300
1
ON=1, OFF=0
Unsigned
R/W