Communication with Modbus
A43/A44 124 2CMC48001M0201
User Manual Revision: C
Pulse input
counters
Quantity
OBIS code
Active energy import L3
1.0.61.8.0.255
Active energy export L1
1.0.22.8.0.255
Active energy export L2
1.0.42.8.0.255
Active energy export L3
1.0.62.8.0.255
Active energy net L1
1.0.36.8.0.255
Active energy net L2
1.0.56.8.0.255
Active energy net L3
1.0.76.8.0.255
Reactive energy import L1
1.0.23.8.0.255
Reactive energy import L2
1.0.43.8.0.255
Reactive energy import L3
1.0.63.8.0.255
Reactive energy export L1
1.0.24.8.0.255
Reactive energy export L2
1.0.44.8.0.255
Reactive energy export L3
1.0.64.8.0.255
Reactive energy net L1
1.0.129.8.0.255
Reactive energy net L2
1.0.130.8.0.255
Reactive energy net L3
1.0.131.8.0.255
Apparent energy import L1
1.0.29.8.0.255
Apparent energy import L2
1.0.49.8.0.255
Apparent energy import L3
1.0.69.8.0.255
Apparent energy export L1
1.0.30.8.0.255
Apparent energy export L2
1.0.50.8.0.255
Apparent energy export L3
1.0.70.8.0.255
Apparent energy net L1
1.0.138.8.0.255
Apparent energy net L2
1.0.139.8.0.255
Apparent energy net L3
1.0.140.8.0.255
The following table lists the OBIS codes for pulse input counters:
Quantity
OBIS code
Input 1 counter
1.128.82.8.0.255
Input 2 counter
1.129.82.8.0.255
Input 3 counter
1.130.82.8.0.255
Input 4 counter
1.131.82.8.0.255