Communication with Modbus
A43/A44 138 2CMC48001M0201
User Manual Revision: C
Structure of
the data block
The log is read by repeatedly loading new values into the data block in
backward or forward direction in time.
The event appearing in the first position in the data block has the entry number
indicated by Entry number register. In case of backwards reading the events in
the other positions follow in ascending entry number order, i.e. going towards
older events. In case of forward reading the events in the other positions follow
in descending entry number order, i.e. going towards more recent events.
The following table describes the structure of the data block:
Entry
Contents
Start
Size
Description
position
Reg
(Hex)
1
Timestamp
6510
3
Date and time when the event occur ed
(Date/Time format)
1
Category
6513
1
The category of this log entry (exception,
warning, error or information).
1
Event id
6514
1
The id for this log entry, identifying what
has happened.
1
Duration
6515
2
The duration of this event measured in
seconds.
...
...
15
Timestamp
6572
3
Date and time when the event occur ed
(Date/Time format)
15
Category
6575
1
The category of this log entry (exception,
warning, error or information).
15
Event id
6576
1
The id for this log entry, identifying what
has happened.
15
Duration
6577
2
The duration of this event measured in
seconds.
Category
Possible values for the category register are shown in the table below:
Category
Description
1
Exception
2
Error
4
Warning
8
Information