Communication with M-Bus
2CMC48001M0201 215 A43/A44
Revision: C User Manual
Byte No.
Size
Value
Description
61
1
F2
VIFE resettable energy
62
1
xx
VIFE status
63-68
6
xxxxxxxxxxxx
Resettable reactive exported energy, Total
69
1
04
DIF size, 32 bit integer
70
1
FF
VIFE next byte is manufacturer specific
71
1
F1
VIFE reset counter
72
1
xx
VIFE status
73-76
4
xxxxxxxx
Reset counter for active imported energy, Total
77
1
84
DIF size, 32 bit integer
78
1
40
DIFE (Unit = 1)
79
1
FF
VIFE next byte is manufacturer specific
80
1
F1
VIFE reset counter
81
1
xx
VIFE status
82-85
4
xxxxxxxx
Reset counter for active exported energy, Total
86
1
84
DIF size, 32 bit integer
87
1
80
DIFE
88
1
40
DIFE (Unit = 2)
89
1
FF
VIFE next byte is manufacturer specific
90
1
F1
VIFE reset counter
91
1
xx
VIFE status
92-95
4
xxxxxxxx
Reset counter for reactive imported energy, Total
96
1
84
DIF size, 32 bit integer
97
1
C0
DIFE (Unit = 1)
98
1
40
DIFE (Unit = 2)
99
1
FF
VIFE next byte is manufacturer specific
100
1
F1
VIFE reset counter
101
1
xx
VIFE status
102-105
4
xxxxxxxx
Reset counter for reactive exported energy, Total
106
1
0E
DIF size, 12 digit BCD
107
1
FF
VIFE next byte is manufacturer specific
108
1
F9
VIF extension of manufacturer specific VIFE's
109
1
C4
Energy in CO2 with resolution 0,001 kg
110
1
xx
VIFE status
111-116
6
xxxxxxxxxxxx
CO2 for active imported energy, Total
117
1
0E
DIF size, 12 digit BCD
118
1
FF
VIFE next byte is manufacturer specific
119
1
F9
VIF extension of manufacturer specific VIFE's
120
1
C9
Energy in Currency with resolution 0,01 currency
121
1
xx
VIFE status
122-127
6
xxxxxxxxxxxx
Currency for active imported energy, Total
128
1
04
DIF size, 32 bit integer

Table of Contents