EasyManua.ls Logo

ABB A43

ABB A43
295 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication with M-Bus
2CMC48001M0201 241 A43/A44
Revision: C User Manual
0E ED EB 00 00 15 00 16 08 14 ;Date/time stamp for
maximum given above: 16:th of august 2014, 00:15:00
14 A9 FF 81 FF F9 D1 00 40 11 00 00 ;Current demand (storage number 0)
for 1:st maximum L1 active power import, VIF A9 -> data in VA with 2
decimals. Data = 1140hex = 44.16 W
0E ED EB 00 00 15 00 16 08 14 ;Date/time stamp for maximum given
above: 16:th of august 2014, 00:15:00
14 FD C8 FF 81 FF F9 D1 00 97 07 00 00 ;Current demand (storage number
0) for 1:st maximum L1-N voltage, VIF C8 -> data in V with 1 decimal.
Data = 797hex = 194.3 V
0E ED EB 00 00 30 00 16 08 14 ;Date/time stamp for maximum given
above: 16:th of august 2014, 00:30:00
12 FF EE FF 81 FF F8 80 FF F9 D1 00 0D 00 ;Current demand (storage
number 0) for 1:st maximum L1-N voltage THD (given in % with 1
decimal). Data = Dhex = 1.3 %
0E ED EB 00 00 15 00 16 08 14 ;Date/time stamp for maximum given
above: 16:th of august 2014, 00:15:00
14 FD D9 FF 81 FF F9 D9 00 F1 00 00 00 ;Current demand (storage number
0) for 1:st maximum sliding L1 current. VIFE D9 -> data in A with
3decimals. Data = F1hex = 0.241 A
0E ED EB 00 00 15 00 16 08 14 ;Date/time stamp for maximum given
above: 16:th of august 2014, 00:15:00
12 FF ED FF 81 FF F8 80 FF F9 D1 00 7E 00 ;Current demand (storage
number 0) for 1:st maximum L1 current THD (given in % with 1 decimal).
Data = 7Ehex = 12.6 %
0E ED EB 00 00 15 00 16 08 14 ;Date/time stamp for maximum given
above: 16:th of august 2014, 00:15:00
94 10 A9 FF F9 D1 00 66 33 00 00 ;Current demand (storage number 0)
for 1:st maximum active T1 power. VIFE A9 -> data in W with 2
decimals. Data = 3366hex = 131.58 W
0E ED EB 00 00 15 00 16 08 14 ;Date/time stamp for maximum given
above: 16:th of august 2014, 00:15:00
0E ED EB FF F0 00 05 42 00 16 08 14 ;Date/time stamp for end of
measurement period. Will always be current date and time for the
currently pending period, in this case 16:th of august 2014, 00:42:05
1F ;Dif 1F -> More data exists
A5 16 ;Checksum and stop byte
System sends out request UD2:
10 7B FE 79 16
Meter sends out data telegram 3:
68 54 54 68 08 00 72 34 12 00 00 42 04 20 02 B4 00 00 00 ;Data header

Table of Contents

Other manuals for ABB A43

Related product manuals