EasyManua.ls Logo

ABB A43

ABB A43
295 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication with M-Bus
2CMC48001M0201 263 A43/A44
Revision: C User Manual
Example 2, readout of current harmonic data starting from phase 2
System sends current harmonic data read request command
68 08 08 68 73 FE 51 01 FF F9 1B 02 D8 16
Meter sends out acknowledge:
E5
System sends out request UD2:
10 7B FE 79 16
Meter sends out data telegram:
68 C0 C0 68 08 02 72 34 12 00 00 42 04 20 02 1C 00 00 00 ;Data header
02 FF ED FF 82 FF F8 80 00 2A 01 ;Total current harmonic distorsion for
phase 2 = 29.8 %
02 FF ED FF 82 FF F8 82 00 18 00 ;2:nd current harmonic distorsion for phase
2 = 2.4 %
02 FF ED FF 82 FF F8 83 00 4D 00 ;3:rd current harmonic distorsion for phase
2 = 7.7 %
02 FF ED FF 82 FF F8 84 00 48 00 ;4:th current harmonic distorsion for phase
2 = 7.2 %
02 FF ED FF 82 FF F8 85 00 2F 00 ;5:th current harmonic distorsion for phase
2 = 4.7 %
02 FF ED FF 82 FF F8 86 00 18 00 ;6:th current harmonic distorsion for phase
2 = 2.4 %
02 FF ED FF 82 FF F8 87 00 79 00 ;7:th current harmonic distorsion for phase
2 = 12.1 %
02 FF ED FF 82 FF F8 88 00 57 00 ;8:th current harmonic distorsion for phase
2 = 8.7 %
02 FF ED FF 82 FF F8 89 00 58 00 ;9:th current harmonic distorsion for phase
2 = 8.8 %
02 FF ED FF 82 FF F8 8A 00 1C 00 ;10:th current harmonic distorsion for
phase 2 = 2.8 %
02 FF ED FF 82 FF F8 8B 00 1A 00 ;11:th current harmonic distorsion for
phase 2 = 2.6 %
02 FF ED FF 82 FF F8 8C 00 86 00 ;12:th current harmonic distorsion for phase
2 = 13.4 %
02 FF ED FF 82 FF F8 8D 00 1C 00 ;13:th current harmonic distorsion for
phase 2 = 2.8 %
02 FF ED FF 82 FF F8 8E 00 36 00 ;14:th current harmonic distorsion for phase
2 = 5.4 %
02 FF ED FF 82 FF F8 8F 00 49 00 ;15:th current harmonic distorsion for phase
2 = 7.3 %
02 FF ED FF 82 FF F8 90 00 7F 00 ;16:th current harmonic distorsion for phase
2 = 12.7%
1F ; Dif 1F -> More harmonic data exist 69 16 ;Checksum an stopbyte