ACQ550-U1 User’s Manual 117
Parameters
2208 EMERG DEC TIME
Sets the deceleration time for maximum frequency to zero for an emergency.
See parameter 2109
EMERG STOP SEL.
Ramp is linear.
2209 RAMP INPUT 0
Defines control for forcing the speed to 0 with the currently used deceleration ramp (see parameters 2203 DECELER
TIME 1 and 2206 DECELER TIME 2).
0 =
NOT SEL – Not selected.
1 =
DI1 – Defines digital input DI1 as the control for forcing the speed to 0.
Activating the digital input forces the speed to zero, after which the speed will stay at 0.
De-activating the digital input: speed control resumes normal operation.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for forcing the speed to 0.
•See
DI1 above.
7 =
COMM – Defines bit 13 of the Command Word 1 as the control for forcing the speed to 0.
The Command Word is supplied through fieldbus communication.
The Command Word is parameter 0301.
-1 =
DI1(INV) – Defines inverted digital input DI1 as the control for forcing the speed to 0.
De-activating the digital input forces the speed to 0.
Activating the digital input: speed control resumes normal operation.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the control for forcing the speed to 0.
•See
DI1(INV) above.