ACQ550-U1 User’s Manual 139
Parameters
Code Description
3601 TIMERS ENABLE
Selects the source for the timer enable signal.
0 = NOT SEL – Timed functions are disabled.
1 =
DI1 – Defines digital input DI1 as the timed function enable signal.
• The digital input must be activated to enable the timed function.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the timed function enable signal.
7 =
ACTIVE – Timed functions are enabled.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the timed function enable signal.
• This digital input must be de-activated to enable the timed function.
•-2…-6 = DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the timed function enable signal.
3602 START TIME 1
Defines the daily start time.
• The time can be changed in steps of 2 seconds.
• If parameter value is 07:00:00, the timer is activated
at 7 a.m.
• The figure shows multiple timers on different
weekdays.
3603 STOP TIME 1
Defines the daily stop time.
• The time can be changed in steps of 2 seconds.
• If the parameter value is 09:00:00, the timer is deactivated at 9 a.m.
3604 START DAY 1
Defines the weekly start day.
1 =
MONDAY…7 = SUNDAY
• If parameter value is 1, timer 1 weekly is active from Monday midnight (00:00:00).
3605 STOP DAY 1
Defines weekly stop day.
1 =
MONDAY…7 = SUNDAY
• If parameter value is 5, timer 1 weekly is deactivated on Friday midnight (23:59:58).
3606 START TIME 2
Defines timer2 daily start time.
• See parameter 3602.
3607 STOP TIME 2
Defines timer 2 daily stop time.
• See parameter 3603.
3608 START DAY 2
Defines timer 2 weekly start day.
• See parameter 3604.
3609 STOP DAY 2
Defines timer 2 weekly stop day.
• See parameter 3605.
3610 START TIME 3
Defines timer 3 daily start time.
• See parameter 3602.
3611 STOP TIME 3
Defines timer 3 daily stop time.
• See parameter 3603.
Mon Tue Wed Thu Fri Sat Sun
00:00:00
09:00:00
10:30:00
12:00:00
13:00:00
15:00:00
17:00:00
20:30:00
Time period 1
Time period 2
Time period 3
Time period 4