19…21
RO1
22…24
RO2
25…27
RO3
EFB
EIA/R5-485
34…38
STO
40, 41
Ext. 24 V
10…12
24 V
GND
13…15
DI
16…18
DI
1…3
AI1
4…6
AI2
7…8
AO
SLOT 1
SLOT 2
2
1
Isolation areas
Panel port1
Power unit connection at the bottom of the control unit2
Reinforced insulation (IEC/EN 61800-5-1:2007, UL 61800-
5-1 First edition)
Functional insulation (IEC/EN 61800-5-1:2007, UL 61800-
5-1 First edition)
The terminals on the control board fulfill the Protective Extra Low Voltage
(PELV) requirements (EN 50178): There is reinforced insulation between the
user terminals which only accept ELV voltages and terminals that accept
higher voltages (relay outputs).
Note: There is functional insulation also between the individual relay outputs.
Note: There is reinforced insulation on the power unit.
120 Control unit