EN - Quick installation and start-up guide 13
EN
ES
PL
TR
ZH
Connection procedure: frames R5...R8
WARNING! If the drive is connected to an IT (non-grounded) system or to a
corner-grounded TN system, disconnect the EMC filter grounding screw and
varistor (VAR) grounding screw.
1. Remove the front cover.
2. Remove the shroud on the power cable terminals by releasing the clips and lifting
the shroud up from the sides with a screwdriver.
3. Knock out holes in the shroud for the cables to be installed.
4. Frame R8 only
: If you install parallel cables, also knock out holes in the lower
shroud for the cables to be installed.
5. Cut an adequate hole into the rubber grommet. Slide the grommet onto the cable.
6. Strip the motor cable.
7. Slide the cables through the holes of the lead-through plate and attach the
grommets to the holes (the motor cable to the right and the input power cable to
the left).
8. Ground the motor cable shield under the grounding clamp.
1
2
4
Frame 8
3
ACQ80R0-R8 QIG.book Page 13 Friday, February 1, 2019 1:18 PM