152 Parameters
14.12 DIO1 ON delay (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Defines the activation delay for digital input/output DIO1.
0.0 s
t
On
= 14.12 DIO1 ON delay
t
Off
= 14.13 DIO1 OFF delay
*Electrical status of DIO (in input mode) or status of selected source (in output mode). Indicated by
14.05 DIO status.
**Indicated by 14.06 DIO delayed status.
0.0…3000.0 s Activation delay for DIO1. 10 = 1 s
14.13 DIO1 OFF delay (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Defines the deactivation delay for digital input/output
DIO1. See parameter 14.12 DIO1 ON delay.
0.0 s
0.0…3000.0 s Deactivation delay for DIO1. 10 = 1 s
14.14 DIO2 function (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Selects whether DIO2 of the extension module is used as
a digital input or output.
Input
Output DIO2 is used as a digital output. 0
Input DIO2 is used as a digital input. 1
14.15 DIO2 filter gain (Visible when 14.01 Module 1 type = FIO-11)
Determines a filtering time for DIO2 when it is used as an
input.
7.5 us
7.5 us 7.5 microseconds. 0
195 us 195 microseconds. 1
780 us 780 microseconds. 2
4.680 ms 4.680 milliseconds. 3
14.16 DIO2 output source (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Selects a drive signal to be connected to digital
input/output DIO2 when parameter 14.14 DIO2 function is
set to Output.
For the available selections, see parameter 14.11 DIO1
output source.