Parameters 273
Motor speed used 01.01 Motor speed used (page 105). 1
Output frequency 01.06 Output frequency (page 105). 3
Motor current 01.07 Motor current (page 105). 4
Motor torque 01.10 Motor torque (page 105). 6
DC voltage 01.11 DC voltage (page 105). 7
Power inu out 01.14 Output power (page 106). 8
Speed ref ramp in 23.01 Speed ref ramp input (page 203). 10
Speed ref ramped 23.02 Speed ref ramp output (page 204). 11
Speed ref used 24.01 Used speed reference (page 210). 12
Torq ref used 26.02 Torque reference used 13
Freq ref used 28.02 Frequency ref ramp output (page 226). 14
Other Source selection (see Terms and abbreviations on
page 101).
-
36.02 PVL filter time Defines a filtering time for the peak value logger. See
parameter 36.01 PVL signal source.
2.00 s
0.00…120.00 s Peak value logger filtering time. 100 = 1 s
36.06 AL2 signal source Selects the signal to be monitored by amplitude logger 2.
The signal is sampled at 200 ms intervals.
The results are displayed by parameters 36.4036.49.
Each parameter represents an amplitude range, and
shows what portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter 36.07
AL2 signal scaling.
Amplitude logger 2 can be reset using parameter 36.09
Reset loggers. The date and time of the last reset are
stored into parameters 36.50 and 36.51 respectively.
For the selections, see parameter 36.01 PVL signal
source.
Motor torque
36.07 AL2 signal scaling Defines the signal value that corresponds to 100%
amplitude.
100.00
0.00…32767.00 Signal value corresponding to 100%. 1 = 1
36.09 Reset loggers Resets the peak value logger and/or amplitude logger 2.
(Amplitude logger 1 cannot be reset.)
Done
Done Reset completed or not requested (normal operation). 0
All Reset both the peak value logger and amplitude logger 2. 1
PVL Reset the peak value logger. 2
AL2 Reset amplitude logger 2. 3
36.10 PVL peak value Displays the peak value recorded by the peak value
logger.
0.00
-32768.00…32767.00 Peak value. 1 = 1
36.11 PVL peak date Displays the date on which the peak value was recorded. -
- Peak occurrence date. -
36.12 PVL peak time Displays the time at which the peak value was recorded. -
- Peak occurrence time. -
No. Name/Value Description Def/
FbEq16