Note: If the default IP address is used on a network, it can cause an IP Address conflict if the network’s
subnet mask is
10.0.0.0/8
(see
Subnetwork (Subnet)
on page 7).
It may be possible to reach the CBXi over the network but BACnet messaging may fail.
In this case you may need to use a directly-connected laptop, or a different network to configure
the CBXi. Alternatively you could change the CBXi’s subnet mask to
10.ss.ss.ss/24
, (where
ss
is the
serial number) to reduce the size of the subnet that could give rise to conflicts. For example, a
CBXi with serial number
901001A
should have a subnet mask of
10.90.10.01/24
.
Accessing the CBXi’s Web UI
Point a web browser at the CBXi device’s IP address, and log in to the Web UI.
Note: By default, all CBXi devices leaving the factory are configured with the following login:
username:
admin
password:
cylonctl
It is recommended that you change these credentials by clicking on the User icon in the top-right of the
Web UI page and selecting
Change Password
.