29
8
OFF
IAt.4
2..12
OFF
IAt..2
2.10
OFF
IAt.1
2.09
•2
•3
•1
100.0
Pb-2
2.06
100.0
Pb-1
2.05
Pb-4
2.08
100.0
•3
OFF
drV1
2.13
•1
•2
2.05...2.13
3 SET UP MODE
3.2 Level 2 Tune
•1 Heat/cool outputs use a common proportional band. The default is 'Pb-1'.
•2 Displayed only if a tune parameter source is selected – see Section 4.2, Basic Configuration/
Template Application and Section 4.6, Control Configuration/ Tune Parameter Source.
•3 Displayed only if a tune parameter source is selected – see Section 4.6, Control Configuration/
Tune Parameter Source.
Proportional Band 1
Enter the value for Proportional Band 1.
[0.1% to 999.9%]
'Pb-1' is the default proportional band
Proportional Band 2, 3 and 4
Enter the value for Proportional Band 2, 3 and/or 4.
[0.1% to 999.9%]
Integral Action Time 1
[1 to 7200 seconds or 'OFF']
'IAt.1' is the default integral action time.
Integral Action Time 2, 3 and 4
[1 to 7200 seconds or 'OFF']
Derivative Action Time 1
[0.1 to 999.9 seconds or 'OFF']
Continued on next page.