46
4.3 Level 7 Analog Inputs 7.15...7.21
Analog Input Type & Electrical Range (I/P3)
Temperature Units
C THC readings displayed in °C
F THC readings displayed in °F
Decimal Places
0 XXXX
1 XXX.X
2 XX.XX
3 X.XXX
Engineering High
[–999 to 9999]
Note. This parameter defaults to the maximum allowed value when
THC or RTD inputs are selected – see Table 4.1.
Engineering Low
[–999 to 9999]
Note. This parameter defaults to the minimum allowed value when
THC or RTD inputs are selected – see Table 4.1.
Broken Sensor Drive (I/P3)
NONE No action. Actual input values remain valid.
UP Input driven to the maximum upscale value (999)
dN Input driven to the minimum downscale value (–999)
Filter Time Constant (I/P3)
The input values are averaged over the time set.
[0 to 60 seconds]
Return to top of page.
4 CONFIGURATION MODE
•1 Frames 7.16 to 7.21 are not displayed if Analog Input Type 3 is set to 'OFF'.
•2 Displayed only if THC or RTD input types are selected.
•3 When i/p 2 is assigned to a remote set point input, it is displayed with the same number of decimal places as
the associated process variable.
1000
En3.H
7...18
0
dP.3
7...17
C
UNt3
7..16
2
tYP.3
7.15
0
En3.L
7...19
•1
•2
UP
bSd.3
7.20
0
FLt.3
7.21
LEV7
INPt
•3
yalpsiDnoitpircseDyalpsiDnoitpircseD
FFO
desUtoN
1
Am02ot0
b
BepyTCHT
2
Am02ot4
E
EepyTCHT
3
V5ot0
J
JepyTCHT
4
V5ot1
K
KepyTCHT
6
Vm05ot0
L
LepyTCHT
7
reziraeniltoorerauqsAm02ot4
N
NepyTCHT
8
2/3rewopAm02ot4
r
RepyTCHT
9
2/5rewopAm02ot4
S
SepyTCHT
11
rofkcabdeefecnatsiseR
t
TepyTCHTevlavdezirotom
P
DTR001TP
U
motsuC