EasyManua.ls Logo

ABB ETL600 - Page 302

ABB ETL600
382 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Revision: Language: Page:
A EN 16/37
1KHW001493-EN
Now contacts at terminal, telephony, 6b-7a should be open and contacts 6a-6b should be
closed. Check it.
4. Check PAX-BLOCKING relay. In normal operation contacts at terminal, telephony, 6b-7a
should be closed and contacts 6a-6b should be open.
Switch off the remote equipment, after the programmed delay time the link alarm occurs.
Now contacts at terminal, telephony, 6b-7a should be open and contacts 6a-6b should be
closed.
B.10.6 Pax 4-wire, remote is Pax 4-wire
The following tests must only be done, if the operation mode ‘Pax 4-wire’ is configured at the local
equipment and the operation mode ‘Pax 4-wire’ is selected at the remote equipment.
1. Toggling the M-WIRE at remote equipment, E-WIRE output should toggle simultaneously
at local equipment. Note, E-WIRE is a switching contact without inherent voltage source
and without polarity.
2. Activate M-WIRE at both equipments. If M-WIRE is configured as ‘inverted’, contacts at
terminal, telephony, 4a-4b must be opened, otherwise closed.
3. Feed a 800 Hz tone, with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in 1 dB range
of the configured output level from the local equipment.
4. Check PAX-BLOCKING relay. In normal operation contacts at terminal, telephony, 6b-7a
should be closed and contacts 6a-6b should be open.
Switch off the remote equipment, after the programmed delay time the link alarm occurs.
Now contacts at terminal, telephony, 6b-7a should be open and contacts 6a-6b should be
closed.
B.10.7 Pax 4-wire, remote is ‘Remote subscriber’
The following tests must only be done, if the operation mode ‘Pax 4-wire’ is configured at the local
equipment and the operation mode ‘Remote subscriber’ is selected at the remote equipment.
1. Toggling the hook contact of remote equipment, E-WIRE output should toggle
simultaneously at local equipment. Switching of hook contact can simulated by closing
the subscriber contacts at terminal, telephony, 0a-0b. Note, E-WIRE is a switching
contact without inherent voltage source and without polarity.
2. Check the Output level of speech:
Instead of subscriber, use coupling bridge similar to that, shown in Figure 2. The resistor
R should be chosen to 500 , included the resistance of the two coils. If the coupling
bridge has polarity. Check first polarity at terminal, telephony, 0a-0b.
3. Activate M-WIRE at local equipments. If M-WIRE is configured as ‘inverted’, contacts at
terminal, telephony, 4a-4b must be opened, otherwise closed.
4. Feed a 800 Hz tone, with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in 1 dB range
of the configured output level from the local equipment.
5. Check PAX-BLOCKING relay. In normal operation contacts at terminal, telephony, 6b-7a
should be closed and contacts 6a-6b should be open.
Switch off the remote equipment, after the programmed delay time the link alarm occurs.
Now contacts at terminal, telephony, 6b-7a should be open and contacts 6a-6b should be
closed.
B.10.8 Pax 4/2-wire
The following tests must only be done, if the operation mode ‘Pax 4/2wire’ is configured at both
ends of the link.
1. Toggling the M-WIRE at remote equipment, E-WIRE output should toggle simultaneously
at local equipment. Note, E-WIRE is a switching contact without inherent voltage source
and without polarity.
2. Activate M-WIRE at both equipments. If M-WIRE is configured as ‘inverted’, contacts at
terminal, telephony, 4a-4b must be opened, otherwise closed.
Note: It is assumed, that LOCAL/TRANSIT is deactivated.

Table of Contents

Related product manuals