Communication protocol 149
Example 6: Configuring the process data written to the drive
PROFIdrive parameter 915 can be used to define which data is
written cyclically to a drive parameter as application-specific
process data.
In the example below, the value of drive parameter 12.02
(0Ch.02h) is selected to be taken from PZD3. The parameter will
continue to be updated with the contents of PZD3 in each Request
frame until a different selection is made.
Subindex (IND) defines which process data word (PZD) the
required data is taken from. Parameter Value selects the drive
parameter to which that word is mapped.
Subsequently, the contents of PZD3 in each Request frame are
written to drive parameter 12.02 CONSTANT SPEED 1 until a
different selection is made.
Req
DP header
7
3
9
3
0
3
0
0
0
0
0
0
0
C
0
2
0
4
7
F
3
4
1
5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
DP trailer
Resp 4
3
9
3
0
3
0
0
0
0
0
0
0
C
0
2
0
3
3
7
3
4
1
5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
CW
REF
Request (Change parameter value [array])
Parameter Number (915 decimal)
Subindex (03 = PZD3)
1)
Parameter Value
PZD3 PZD4 PZD5 PZD6
SW
ACT
Parameter Number (915 decimal)
Response (Transfer parameter value [array])
Subindex (03 = PZD3)
1)
Parameter Value
PZD3
PZD4
PZD5
PZD6
1)
2nd byte reserved