EasyManua.ls Logo

ABB FPBA-01 PROFIBUS DP - State Machine

ABB FPBA-01 PROFIBUS DP
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication profiles 115
State machine
The state machine for the ABB Drives communication profile is
shown below.
Power ON (CW Bit0=0)
(SW Bit6=1)
(SW Bit0=0)
from any state
(CW=xxxx x1xx xxxx x110)
(SW Bit1=1)
n(f)=0 / I=0
(SW Bit2=0)
ABCD
(CW Bit3=0)
operation
inhibited
OFF1 (CW Bit0=0)
(SW Bit1=0)
(SW Bit0=1)
(CW Bit3=1
and
SW Bit12=1)
CD
(CW Bit5=0)
(SW Bit2=1)
(SW Bit5=0)
from any state from any state
Emergency stop
OFF3 (CW Bit2=0)
n(f)=0 / I=0
Emergency OFF
OFF2 (CW Bit1=0)
(SW Bit4=0)
B
BCD
(CW Bit4=0)
(CW=xxxx x1xx xxx1 1111)
(CW=xxxx x1xx xx11 1111)
D
(CW Bit6=0)
A
C
(CW=xxxx x1xx x111 1111)
(SW Bit8=1)
D
from any state
Fault
(SW Bit3=1)
(CW Bit7=1)
(CW=xxxx x1xx xxxx x111)
(CW=xxxx x1xx xxxx 1111
and SW Bit12=1)
state
condition
rising edge
the bitof
ABB Drives
communication
profile
CW = Control
word
SW = Status
word
n = Speed
RFG: OUTPUT
ENABLED
OFF2
ACTIVE
OFF3
ACTIVE
OPERATION
FAULT
READY TO
OPERATE
READY TO
SWITCH ON
NOT READY TO
SWITCH ON
SWITCH-ON
INHIBITED
OPERATION
INHIBITED
OFF1
ACTIVE
OPERATION
ENABLED
RFG: ACCELERATOR
ENABLED
MAINS OFF

Table of Contents

Related product manuals