Communication profiles 113
Status word contents
The table below shows the contents of the Status word for the ABB
Drives communication profile. The upper case boldface text refers
to the states shown on page 115.
10 REMOTE_
CMD
1 Fieldbus control enabled
0 Control word and reference not getting
through to the drive, except for CW bits
OFF1, OFF2 and OFF3.
11 EXT_CTRL_
LOC
1 Select External Control Location EXT2.
Effective if control location parameterized
to be selected from fieldbus.
0 Select External Control Location EXT1.
Effective if control location parameterized
to be selected from fieldbus.
12…
15
Drive-specific (For information, see the drive documentation.)
Bit Name Value STATE/Description
0 RDY_ON 1 READY TO SWITCH ON
0 NOT READY TO SWITCH ON
1 RDY_RUN 1 READY TO OPERATE
0OFF1 ACTIVE
2 RDY_REF 1 OPERATION ENABLED
0 OPERATION INHIBITED
3 TRIPPED 1 FAULT
0 No fault
4 OFF_2_STA 1 OFF2 inactive
0OFF2 ACTIVE
5 OFF_3_STA 1 OFF3 inactive
0OFF3 ACTIVE.
6SWC_ON_
INHIB
1 SWITCH-ON INHIBITED
0–