Communication protocol 161
15h Response too long The length of the current response
exceeds the maximum
transmittable length.
16h Parameter address
impermissible
Illegal value or value that is not
supported for the attribute, number
of elements, parameter number or
sub-index, or a combination
17h Illegal format Write request: Illegal format or
format of parameter data that is not
supported
18h Number of values
inconsistent
Write request: Number of values of
parameter data does not match
number of elements at the
parameter address
65h…FF Manufacturer-specific
error area
65h Vendor-specific error Vendor-specific error
66h Request not supported Request not supported
67h Communication error Request cannot be completed
because of a communication error.
6Eh Non-volatile error Failure during write to non-volatile
memory
6Fh Time-out error Request aborted because of
timeout
78h PZD map failure Parameter cannot be mapped to
PZD (size mismatch or non-
existent).
79h PZD memory failure Parameter cannot be mapped to
PZD (out of memory).
7Ah Multiple PZD map Parameter cannot be mapped to
PZD (multiple PZD write).
82h Control word bit map Cannot map Control word bit
(parameter 933…937, eg, double
mapping of bits).
8Ch Set torque mode error Cannot change mode to TORQUE
(frequency is used).