76 Start-up
(ACQ810 only)
50.21 Comm loss
enable
bit 0 = 1 Enables communication loss
detection for EXT 1.
51.01 FBA type Profibus-DP
1)
Displays the type of the
fieldbus adapter module.
51.02 FBA par2
(NODE ADDRESS)
3
2)
Defines the PROFIBUS node
address of the fieldbus adapter
module.
51.03 FBA par3
(BAUD RATE)
12000
1)
Displays the current baud rate
on the PROFIBUS network in
kbit/s.
51.04 FBA par4
(TELEGRAM TYPE)
2 (= PPO2)
1)
Displays the telegram type
selected by the PLC
configuration tool.
51.05 FBA par5
(PROFILE)
0 (= PROFIdrive) Selects the Control word
according to the PROFIdrive
profile (speed control mode).
52.01 FBA data in1 4 (= SW 16bit)
1)
Status word
52.02 FBA data in2 5 (= Act1 16bit) Actual value 1 (speed)
52.03 FBA data in3 122
2)
Power (32-bit)
52.05 FBA data in5 107
2)
DC bus voltage (32-bit)
53.01 FBA data out1 1 (= CW 16bit)
1)
Control word
53.02 FBA data out2 2 (= Ref1 16bit) Reference 1 (speed)
53.03 FBA data out3 2606
2)
Constant speed 1 (32-bit)
53.05 FBA data out5 2607
2)
Constant speed 2 (32-bit)
51.27 FBA par
refresh
Refresh Validates the FPBA-01
configuration parameter
settings.
Drive parameter Setting for
ACS850/
ACQ810 drives
Description