80 FEP630, FEH630 ELECTROMAGNETIC FLOWMETER | OI/FEP630/FEH630-EN REV. D
… 8 Operation
… Parameter descriptions
Menu: Device Info
This menu is only used to display the device parameters. The parameters are displayed independently of the configured access level,
but cannot be changed.
Menu / parameter Description
Device Info
...Sensor Selection of submenu ‘...Sensor’ using .
...Transmitter Selection of submenu ‘...Transmitter’ using .
Device Info / ...Sensor
QmaxDN Type For informational purposes only.
Meter Size Nominal diameter of sensor.
Qm Max DN The value is the maximum mass flow at a flow velocity of 10 m/s.
The value is automatically set through the selected nominal diameter, multiplied by the set density.
Qv Max DN The value provides the maximum volume flow at a flow velocity of 10 m/s.
The value is set automatically via the selected nominal diameter.
Mains Frequency Supply frequency for the power supply.
Exitation Freq Frequency used to operate the magnetic coils of the flowmeter sensor.
Coil Current Regul. For service information only.
Set Point Curr. Current used to operate the magnetic coils of the flowmeter sensor.
DC feedback reg. For service information only.
Sensor ID ID number of the sensor.
Sensor Serial No. Serial number of the sensor.
Sensor Run Hours Operating hours of the sensor.
...Se Calibration Selection of submenu ‘...Se Calibration’ using .
Sensor TFE Function Shows if the total filling electrode (TFE) has been activated or deactivated.
Device Info / ...Sensor / ...Se Calibration
Se Span Calibration value in the forward flow (direction) and reverse flow (direction) of the sensor.
Se Zero
First Cal. Date Date of first calibration of sensor (calibration of new device).
Last Cal. Date Date of last calibration of sensor.
Cal. Cert. No. Identification (number) of the relevant calibration certificate.
First Cal. Location Place of first calibration of the sensor.
Last Cal. Location Place of last calibration of sensor.